Recursos
Contact Resistance Testing of Circuit Breakers — Micro-Ohm Method
2026年06月08日
Worn breaker contacts overheat and fail to interrupt. Micro-ohm testing finds them at maintenance.
The Contact That Quietly Degrades
Every time a circuit breaker interrupts a fault, its contacts erode a little. Over years of operations they pit, oxidise, and lose contact pressure, raising their resistance. A high-resistance contact runs hot, accelerates its own decline, and in the worst case fails to carry or interrupt current. Contact resistance testing with a micro-ohmmeter quantifies this wear at routine maintenance, long before it becomes dangerous.
1. Why a Micro-Ohmmeter
A healthy breaker contact measures tens to low hundreds of micro-ohms. Only a four-wire (Kelvin) micro-ohmmeter injecting a high test current can resolve that range and ignore lead resistance.
- Four-wire method eliminates lead and probe resistance.
- High test current (10 A or more) mimics service conditions.
- Resolution in single micro-ohms.
2. The Test Procedure
- Isolate, lock out, and earth the breaker.
- Close the breaker contacts.
- Connect current leads outboard, potential leads inboard of the contact.
- Inject current and read the resistance across the contact.
- Repeat for each pole.
3. Interpreting Results
- Compare against the manufacturer's maximum contact resistance.
- Compare poles against each other — one pole much higher is suspect.
- Compare against the previous test — a rising trend signals wear.
- A reading 50% above the others or the limit warrants service.
4. Common Causes of High Readings
- Contact erosion from repeated fault interruption.
- Oxidation on contacts that rarely operate.
- Weak contact springs reducing pressure.
- Loose terminal connections (test those separately).
5. After Service
After cleaning or replacing contacts and re-torquing terminals, re-measure. Resistance should return to the expected range. Record before and after values in the maintenance log.
EK Recommendation
EK micro-ohm meters use the four-wire Kelvin method with selectable test current for breaker contacts, busbar joints, and weld quality. Combine with a thermal survey for a full switchgear health assessment. Talk to EK service teams.