EK-A100D Non-contact Phase Sequence Meter
EK Instruments EK-A100D is a professional non-contact phase sequence meter. Designed for industrial electrical measurement and field testing. Built with precision engineering and reliable components for long-term stability.
Product Function
Phase sequence detection (positive phase, reversed phase, default phase), live line inspection, simple electrical inspection, fire line identification, default phase judgment, broken line location search, DC circuit breakpoint detection, circuit line maintenance.
Product features
1.Adopt clamp type non-contact induction measurement, no need to peel off the cable skin, no need to contact the high voltage bare live line. The phase sequence can be detected by directly clamping three ultra-induction and high insulation clamps on the insulation skin of three-phase fire wire respectively.
2.Non-contact measurement, safe and fast,improve working efficiency.
3.Dynamic audible and visual indicate the positive phase or reversed phase state of three-phase power phase sequence, clear and obvious.
4.The meter button plate equip with 4PCS magnet(optional), which can absord on the metal shell of the device in testing, convenient to operate.
Technical Specification
Model | EK-A100C | EK-A100D |
Available Clamp Wire Diameter | ø1.6mm~ø16mm | ø10mm~ø40mm |
Meter Weight | About 0.33kg(include accessories) | About 0.36kg(include accessories) |
Power Supply | DC 3V alkaline dry batteries (LR6 1.5VX2PCS) | |
Live Power Range | AC 70V~1000V, 45Hz-65Hz (Sine Wave Continuous Input) | |
LED Display | [Positive Phase] The phase detector lamp lights up clockwise [Reversed Phase ] The phase detector lamp lights up counter clockwise [Live Power] L1, L2, L3 lamps light up in setting voltage range [Default Phase] L1 or L2, or L3 lamp is not lighting [Open Circuit] L1 or L2, or L3 lamp is not lighting | |
Buzzer | [Positive Phase] the buzzer sounds intermittently [Reversed Phase] the buzzer sounds continuously | |
Battery Check | The POWER indicator lights up after starting up, and the LOW BATTERY indicator lights up when low battery | |
Magnet | The meter back plate equip with 4PCS magnet(optional), which can absord on the distribution box, load weight 800g | |
Automatic Shutdown | 5 minutes without any operation after starting up, the meter will automatic shutdown | |
Max Measure Voltage | AC 1000V | |
Insulation Strength | 5.4kV/rms | |
Max. Rated Power | 300mVA | |
Meter Dimensions | 70mmX75mmX30mm | |
Accessories | Meter:1PCS; Meter bag:1PCS; Lanyard: 1PCS; LR6 battery: 2PCS | |
Applications: Power utility, industrial maintenance, electrical testing labs, field engineering services.